FSPG Pillows

FSPG Fire Pillows are an ideal product to create a temporary or permanent fire barrier around many types of services to prevent the passage of fire through a compartment wall or floor, especially suitable where services are continuously being changed or replaced. FSPG Fire Pillows are filled with organic filler and reactive intumescent additives in a PU glass cloth case.

Pillow

Key Product Points

  • Can be used in rigid walls & floors.

  • Can be used with Metallic Pipes, Cables, Cable Bunches, Cable Trays and Cable Ladders.

  • Reaction Temperature 180oC.

  • High Expansion Ratio.

  • Remains flexible between -20oC to +130oC.

  • Water resistant lining.

  • Suitable for locations up to 1m2.

  • Non-combustible and non-toxic.

  • Ease of installation and long life.

Certifications and Approvals

  • EN 1366-3

  • EN 13501-2

  • EN 10140

  • EN 1026

  • EN ISO 13934-1

  • EN ISO 13935-1

  • BS 476

  • 1121-CPR-JA5008, ETA 13/1056

  • UL-EU-00640-CPR

  • Certifire CF514

Key Installation Points

  • For good adhesion the surfaces of the building elements shall be free of any dust or grease and may need to be primed. On good, clean virgin concrete & masonry, no priming required.

  • Ensure that the aperture and services in question are tested with FSPG Pillows and the site conditions are within the application specification.

  • Upon installation make sure that you install the FSPG Fire Pillow length ways to the recommended installation method for the service you are installing around.

  • Install the FSPG Fire Pillows in such a way that all joints are staggered in each opening around the services to a minimum depth of 150mm. Always ensure that large voids are completely filled and FSPG Pillows are installed in a manner that ensures a tight compression fit.

  • Fill in any gaps with the smaller FSPG PIllows until there are no gaps. Always ensure that large voids are completely filled and fire pillows are installed in a manner that ensures a tight compression fit.

For floor

  • Install a 5mm mild steel mesh securely fastened to rigid floor.

  • Arrange FSPG Pillows in such a manner that they fully fill the penetration voids to a minimum depth of 150mm on the mesh.

  • When cable trunking passes through the seal ensure that the inside is filled with FSPG Sausage Pillows.

Tools Used for Installation

Image icon
DUST PAN & BRUSH
Image icon
PENCIL & RULER